NEWS

Pharmacy

Quality of pharmaceutical production is put by technology and the manufacture organization, including the cleanliness of technological mediums. Since 2000 Miass Factory of Medical Equipment has carried out designing and construction of cleanrooms for different fields of industries. As the base for this direction of activity 10-years-old experience of our factory in creation of cleanrooms for medical units serves...

CLEANROOM

  • Air treatment, decontamination and distribution system;

  • Climate control system;

  • Cleanroom structure (structural elements providing leakproofness);

  • medical, technological and engineering equipment integrated with the cleanroom structure.

 

Filter-fan unit

АМС МЗМО/English Version/Production/Production run equipment/Filter-fan unit

Filter-fan unit

Allocation

Fan-filter unit (ФВМ) - is popular and concerning easy unit, that provides  unidirectional filtered air delivery to the high classes of cleanliness premises.

Application

ФВМ  is used for layout of workspace in medicine, pharmaceucal and other institutions with high level requirements to the air cleanliness (virologic and bacterialogic laboratories, manufacture of ready sterile pharmacy and medical  units, microbiological industries, radioelectrical and other fields of industry).

Construction

FFM consits of:

  • welded steel case, colored by powder paint;
  • rotary economic and rekiable fan (Germany) with back incurved blades with  smooth regulation of rate speed with analog and digital interface;
  •  HEPA (ULPA) air filter, established in a framework from a special aluminium profile;
  • built-on pressure pick-off, that helps to set and support predetermined values  of pure air productivity.

Fan-filter unit

ФВМ construction involves  protecting filter frame from steel perforated sheet inside the cleanroom, module for filter attestation, signal lamp of  filter contamination indication.

It's possible to operate one or several modules from portable control panel.

ФВМ are set to the standard tee girder ceiling cells or to special modules (process chamber, transportable cleanrooms, sluice).

Spеcification

Overall dimension of ФВМ, mm:
1200*600*380
Overall dimenson of filter, mm
1130*530*78
Degree of purification of H14 class filter according to the GOST R 51251-99 against of suspended particulate matter with dimensions of 0,3 mkm and more, %
99,995
Clean air productivity, m3/hour

до 950

Airflow speed 150 mm over a distance from the filter shear, m/s
0,45+/-0,09

Fan features:

  • type
  • consumed power, W
R3G 280
425
Material of ФВМ box
steel, colored by powder paint
Noise level, dB
60
power supply voltage (one fase, 50 Hz), V

230

Weight, kg

60

Ordering variant: Fan-filter unit

Data base:

  • portable control panel;
  • h1, mm - height from the floor to the initial ceiling;
  • h2, mm - height from the floor to the suspended ceiling.