NEWS
|
Equipment
Elements of cleanrooms:
|
Pharmacy
Since 2000 Miass Factory of Medical Equipment has carried out designing and construction of complexes of cleanrooms for different fields of industries. As the base for this direction of activity 15-years-old experience of our factory in creation of cleanrooms for medical units serves...
|
|
|
Low-profile quiet unit
|
|
| АМС МЗМО/English Version/Production/Production run equipment/Ventilation/Low-profile quiet unit
|
Fan unit
Low-prifile quiet fan unit in alone body
|
Allocation
It is made for air delivery or removal in fan systems of cleanrooms or other premises.
Application
Fan unit is used in independent positive-pressure, air cleaning and desinfection systems in premises, that is met exclusive standarts to the noise exposure limit. Unit is placed in limited interceiling space and designed for moving of non-explosive gas-air mixture with temperature no more than 60°C.
Features in using
- Package unit, easily placed in limited ceiling void
- Low noise level
- High productivity
- Sliding control and maintenance of adequate level of air productivity
Fan unit's make up
- Case from galvanized steel with active noise system (or without it);
- Rotary economic and reliable fan (Germany) with back incurved blades;
- Reduser fitting;
- Attachment elements to the initial ceiling.
|

Low-profile quiet fan unit in alone body
|
|

УНМВ-1
|
|
Specification
- Unit is look liked rigid framed structure rectangular in shape , made from thin galvanized sheet with flanged lip in both sides. Frame interiror is encased of acoustic panels. For preventing air flow spin and for loss reduction, at the input and at the exit of the fan, from the left and right are made special battle boards, that provides low noice level in the unit. Used fan allows fluently regulate air productivity from 0 to the maximum level. while using additional control block it is possible to set and automatically support two productivity levels.
- Reducer fittings for setting circular air-duct to the unit are made of 3 types: right, corner, double-sides, with reducer pipes of 250 and 315 mm in diametr. the case of reducer fittings has the same standard flanged lip for connection.
Additional options
- Additional control block that allows to support given level of air productivity;
- Differential pressure cell for fan performance measurement;
- Control panel and indication for one or several units;
- Power supply and signal cable (the length - at the customer's device).
|
 |
Specification of УНМВ-1
|
Overall dimensions, mm
|
680*410*2320 (monoblock with deafenens and reducer fittings)
|
|
Unit productivity for the free head 400 Pa, m3/hour
|
1500
|
|
Maximum noise level within maximum productivity, dB
|
60
|
|
Consumed power, W
|
425
|
|
|
Specification of УНМВ-2
|
Overall dimensions, mm
|
680*410*2320 (monoblock with deafenens and reducer fittings)
|
|
Unit productivity for the free head 400 Pa, m3/hour
|
1500
|
| It is can be added by the set of reducer fittings with one reducing pipe 250 (315) mm or two reducer pipes (right, corner, double-sides, reducer fittings) |
|
Maximum noise level within maximum productivity, dB
|
60
|
|
Consumed power, W
|
425
|
Ordering variant: Low-prifile quiet fan unit in alone body - (numeral acronym)
Data base:
- structure of additional options;
- h1, mm - height from floor to initial ceiling;
- h2, mm - height from the floor to suspended ceiling.
|
|
|
|